4-22 Cabling specifications
#6 AWG wire. The FGND cable connects the SPG/FGE to the FGND stud
located in the MPDC.
The following figure illustrates the ground wire connection for multiple
cabinet and column lineup.
Figure 4-7 Ground wire connection for multiple cabinet and column lineup
EMI expansion
Field made connection.
Lug is already crimped
to the cable

Logic return cabling

All IPECs have home run logic return cables connected to the MPDC battery
return plate.
The following figure illustrates the connection between the logic return cable
and battery return plate.
555-4001-129 Standard 08.01 November 2000
Frame ground from source will be
crimped on site by installers for
SL100 applications.
Lug is crimped and
secured at factory