Honeywell 3G SmartVFD HVFD3D3A0015 Installation And User Manual page 98

Table of Contents

Advertisement

Maximum cross-section to control terminals, flexible wire with
cable end sleeves with collar
Minimum cross-section to control terminals
8.6 Control Input/Output and Control Data
Table 8.19. Digital Inputs.
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic '0' PNP
Voltage level, logic '1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, Ri
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
1) Terminals 27 and 29 can also be programmed as output.
Table 8.20. Analog Inputs.
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, Ri
Max. voltage
Current mode
Current level
Input resistance, Ri
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high voltage
terminals.
31-00559-01
20 AWG [0.5 mm
24 AWG [0.25 mm
4 (6)1)
18, 19, 271), 291), 32, 33
PNP or NPN
0-24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
Approx. 4 kΩ
2
53, 54
Voltage or current
Frame A, B, C: Switch S201 and switch S202
Frame D: Switch A53 and A54
Switch = OFF (U)
-10 to +10 V (scalable)
Approximately 10 kΩ
±20 V
Switch = ON (i)
0/4 to 20 mA (scalable)
Approximately 200 Ω
30 mA
10 bit (+ sign)
Max. error 0.5% of full scale
20 Hz/100 Hz
2
]
2
]
92

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents