Honeywell 3G SmartVFD HVFD3D3A0015 Installation And User Manual page 103

Table of Contents

Advertisement

Recommendations
Use of recommended fuses and circuit breakers ensures possible damage to the
adjustable frequency drive is limited to damages inside the unit. For further infor-
mation, see Application Note Fuses and Circuit Breakers, MN90T.
The fuses below are suitable for use on a circuit capable of delivering 100,000
Arms (symmetrical), depending on the adjustable frequency drive voltage rating.
With the proper fusing the adjustable frequency drive Short Circuit Current Rating
(SCCR) is 100,000 A
8.8.1 CE Compliance
Table 8.27. 200–240 V, Enclosure Types A, B and C.
Enclosure
Type
A2
A3
A5
B1
B2
C1
C2
97
Fuses of the type gG.
Circuit breakers of Moeller types. For other circuit breaker types, ensure that the
energy into the adjustable frequency drive is equal to or lower than the energy
provided by Moeller types.
rms
Power
Recommended
(hp [kW])
Fuse Size
1.5–3
gG-10 (1.5–2 [1.1–
[1.1–2.2]
1.5])
gG-16 (3 [2.2])
4–5
gG-16 (4 [3])
[3.0–3.7]
gG-20 (5 [3.7])
1.5-5
gG-10 (0.34–2 [0.25–
[1.1-3.7]
1.5])
gG-16 (3–4 [2.2–3])
gG-20 (5 [3.7])
7.5–15
gG-25 (7.5 [5.5])
[5.5–11]
gG-32 (10–15 [7.5–
11])
20 [15]
gG-50
25–40
gG-63 (25 [18.5])
[18–30]
gG-80 (30 [22])
gG-100 (40 [30])
50–60
aR-160 (50 [37])
[37–45]
aR-200 (60 [45])
.
Recommended
Recommended
Circuit breaker
Max. Fuse Size
(Moeller)
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-160 (25–
NZMB2-A200
30 [18.5–22])
aR-160 (40
[30])
aR-200 (50
NZMB2-A250
[37])
aR-250 (60
[45])
Max. Trip
Level [A]
25
25
25
63
100
160
250
31-00559-01