WARNING 98, Clock fault
Time is not set or the RTC clock has failed. Reset the clock in 0-70 Date and Time.
WARNING 200, Fire mode
This warning indicates the adjustable frequency drive is operating in Fire mode.
The warning clears when fire mode is removed. See the fire mode data in the alarm
log.
WARNING 201, Fire Mode was Active
This indicates the adjustable frequency drive had entered fire mode. Cycle power to
the unit to remove the warning. See the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in fire mode one or more alarm conditions have been ignored
which would normally trip the unit. Operating in this condition voids unit warranty.
Cycle power to the unit to remove the warning. See the fire mode data in the alarm
log.
WARNING 203, Missing motor
With an adjustable frequency drive operating multi-motors, an underload condi-
tion was detected. This could indicate a missing motor. Inspect the system for
proper operation.
WARNING 204, Locked rotor
With an adjustable frequency drive operating multi-motors, an overload condition
was detected. This could indicate a locked rotor. Inspect the motor for proper oper-
ation.
WARNING 250, New spare part
A component in the adjustable frequency drive has been replaced. Reset the
adjustable frequency drive for normal operation.
WARNING 251, New type code
The power card or other components have been replaced and the type code
changed. Reset to remove the warning and resume normal operation.