Honeywell 3G SmartVFD HVFD3D3A0015 Installation And User Manual page 35

Table of Contents

Advertisement

Table 4.2. Terminal Description.
Terminal
Digital Inputs/Outputs
12, 13
18
19
32
33
27
29
20
Analog Inputs/Outputs
39
42
50
53
54
55
Serial Communication
61
68 (+)
69 (-)
Relays
01, 02, 03
04, 05, 06
Additional terminals:
30
Parameter
Default Setting
+24 V DC
5-10
[8] Start
5-11
[0] No operation
5-14
[0] No operation
5-15
[0] No operation
5-12
[2] Coast
inverse
5-13
[14] JOG
6-50
Speed 0 - High
Limit
+10 V DC
6-1
Reference
6-2
Feedback
8-3
8-3
5-40 [0]
[9] Alarm
5-40 [1]
[5] Running
Two form C relay outputs. Location of the outputs depends on adjustable
frequency drive configuration.
Terminals located on built-in optional equipment. See the manual provided with
the equipment option.
Description
24 V DC supply voltage for digital inputs and external
transducers.
Maximum output current 200 mA for all 24 V loads.
Digital inputs.
For digital input or output. Default setting is input.
Common for digital inputs and 0 V potential for 24 V
supply.
Common for analog output.
Programmable analog output. 0–20 mA or 4–20 mA at
a maximum of 500 Ω
10 V DC analog supply voltage for potentiometer or
thermistor. 15 mA maximum
Analog input. For voltage or current. Switches A53 and
A54 select mA or V.
Common for analog input.
Integrated RC filter for cable shield. ONLY for
connecting the shield in the event of EMC problems.
RS-485 Interface. A control card switch is provided for
termination resistance.
Form C relay output. For AC or DC voltage and resistive
or inductive loads.
31-00559-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents