List Of Warnings And Alarms - Honeywell 3G SmartVFD HVFD3D3A0015 Installation And User Manual

Table of Contents

Advertisement

Trip lock
Input power is cycled. The motor coasts to a stop. The adjustable frequency drive
continues to monitor the adjustable frequency drive status. Remove input power to
the adjustable frequency drive, correct the cause of the fault, and reset the adjust-
able frequency drive.
Warning and Alarm Displays
Figure 7.2. Alarm Display Example.
Status
0.0Hz
Auto Remote Trip
In addition to the text and alarm code in the LCP, there are three status indicator
lights.
Figure 7.3. Status Indicator Lights. .
Status
0.0Hz
Auto Remote Trip
Warning
Alarm
Trip Lock

7.4 List of Warnings and Alarms

The warning/alarm information below defines each warning/alarm condition, pro-
vides the probable cause for the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50. Remove some of the load
from terminal 50, as the 10 V supply is overloaded. Max. 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or improper wiring of the potentiome-
ter can cause this condition.
31-00559-01
A warning is displayed in the LCP along with the warning number.
An alarm flashes along with the alarm number.
0.000kW
0.0Hz
0
Earth Fault [A14]
0.000kW
0.0Hz
0
Earth Fault [A14]
Warning LED
On
Off
On
1(1)
0.00A
1(1)
0.00A
Alarm LED
Off
On (Flashing)
On (Flashing)
61