PA-5400 Series Firewall Installation
STEP 4 |
Remove the four nuts from the ground studs located on the back of the appliance on the
upper left side.
STEP 5 |
Crimp a 6-AWG wire to the provided grounding lug and connect the other end to your earth
ground point.
The crimp tool is not included with the appliance. It is recommended that you use
a Panduit CT-3001/ST crimp tool for this procedure. Refer to the manufacturer's
specifications for more information.
STEP 6 |
Connect the two-post lug connector to the two-post ground studs on the appliance using the
provided nuts and torque each nut to 50 in-lbs. Be careful not to strip the nuts and lug studs.
STEP 7 |
Connect the power supply to a power source based on whether your power supplies are AC
or DC.
(AC Power Supplies
1. Connect the first two power supplies to a 120VAC 15-amp circuit breaker or 240VAC
20-amp circuit breaker using the provided power cords and then connect the second two
PA-5400 Series Next-Gen Firewall Hardware Reference
only)
58
2022 Palo Alto Networks, Inc.
©