Error Display

Display LED is flashing every 0.5 sec or an external connecting
device displays error message while using the product.
This is a warning indicating that the external sensor is OPEN. Cut the power to the unit
and check if the sensor is connected. If abnormality is found in input sensor connection,
disconnect input sensor from controllers and make connection between input (+) terminal
and input (-) terminal in order to check whether current ambient temperature is displayed.
If current ambient temperature is displayed, it can be inferred that the controller is
operating normally. IF HHHH or LLLL is displayed, however, it can be inferred that
problems are found on the controller. Please contact Autonics service center. (This error
check can be available for only thermocouple type.)
© Copyright Reserved Autonics Co., Ltd.
Make sure a proper input sensor has been selected.
TM2 Series
TM4 Series
PWR LED
PWR LED
CH1 LED
CH1 LED
CH2 LED
CH2 LED
-
CH3 LED
-
CH4 LED
Communications output
(decimal number)
Program for PC only
LED Status
When opening the
sensor input
Red light ON
Flashing in red (0.5 sec. intervals)
Flashing in red (0.5 sec. intervals)
Flashing in red (0.5 sec. intervals)
Flashing in red (0.5 sec. intervals)
'31000' output
Display 'OPEN'
7 Troubleshooting Tips
When exceeding the
operational temperature
range
'30000'(high-limit) output
'-30000'(low-limit) output
'HHHH (high-limit)' display
'LLLL (low-limit)' display