MV high/low-limit values for control output can be configured to the actual MV,
provided the temperature controller's MV calculation exceeds the limits.
During heating and cooling control, cooling MV carries a "-" prefix. Therefore, the
high-limit is expressed as a + value on the heating side and the lower limit as a -
value on the cooling side.
Preceding
Group
Condition
Heating
Cooling
Control
Operation
Heating
Group
and
Cooling
Parameter
MV Low-limit
0.0 to (MV High-limit - 0.1)
MV High-limit
(MV Low-limit + 0.1) to 100.0
MV Low-limit
MV High-limit
Same MV will be applied during Auto-tuning.
MV limits are not applied to manual control, MV upon control
stop, MV upon a sensor error, and initial manual control MV.
MV high/low-limit configuration is not available for ON/OFF
control in standard control mode (heating or cooling control).
6 Parameter Settings and Functions
Factory
Range
Default
100.0
-100.0 ~ 0.0
-100.0
0.0 ~ 100.0
100.0
Unit
0.0
%
%
55