Alarm Output - Autonics TM Series User Manual

Multi-channel modular temperature controller
Hide thumbs Also See for TM Series:
Table of Contents

Advertisement

6 Parameter Settings and Functions
6.3.4.2
Auto-tuning Mode Settings
6.4

Alarm Output

66
Auto-tuning is available in Tun1 MODE (SV) or Tun2 MODE (70% of SV), depending
on the baseline value used.
Tun1 Mode [TUN1]: Auto-tunes and calculates a PID time constant based on SV.
Tun2 Mode [TUN2]: Auto-tunes and calculates a PID time constant based on 70% of
SV.
Group
Initial Setting Group
In cooling control mode, TUN2 Mode calculates 70% based at 0°.
Alarm output is a relay output that activates irrespective of control output.
Alarm output works when the temperature of the controlled subject exceeds or falls
below the preset temperature range.
Alarm temperature setting values consist of absolute temperatures or offset
temperatures, depending on the alarm output mode.
Alarm output function is only for TM2 series.
Preceding
Parameter
Condition
PID
Auto-tuning Mode
EX) If SV is -100, executes TUN2 at -70.
© Copyright Reserved Autonics Co., Ltd.
Factory
Range
Default
Tun1
Tun1
Tun2
Unit
-