6 Parameter Settings and Functions
6.2.3

Ramp Settings

Ramp Status by Modes
All modes.
OPEN, HHHH, LLLL, Auto-tuning, Auto→Manual,
RUN→STOP
OPEN, HHHH, LLLL, after Auto-tuning, PV = SV
Power On, SV change, switch from STOP to RUN, switch
from Manual to Auto, Ramp Rate or Ramp time unit
change
56
Ramp is a feature used to configure the slope toward SV (Setting Value). The feature
limits change rate of SV and thereby restricts sudden temperature changes (increase
and decrease) in the control subject.
Ramp is commonly used in applications where rapid temperature changes (increase
and decrease) could impact negatively on the control subject.
Group
Parameter
Ramp_Up[Down]
Control
Change Rate
Operation
Group
Ramp Time Unit
For ceramic or pottery furnaces, rapid heating may break the
furnace subject. Apply Ramp Up Change Rate to control the
temperature.
Operation Status
0 (OFF) to 9999
SEC (seconds), MIN
(minutes), HOUR (hours)
Activating the ramp feature when the ramp is not in operation
limits the rate of SV (Setting Value) change based on PV
(Present Value). Changing SV or ramp parameters when the
ramp is in operation limits the rate of SV change based on SV at
the point of the change.
SV determines the control of the control subject temperature.
The SV changes based on the configured rate of change
(hereinafter referred to as RAMP SV).
Ramp Up change rate and Ramp Down change rate can be set
independently.
Alarm activation with the ramp in operation depends on the final
SV.
Setting the rate of ramp change to 0 deactivates the ramp
feature.
© Copyright Reserved Autonics Co., Ltd.
Factory
Range
Default
MIN
(minute)
RAMP RATE
When 0
Irrespective of
conditions.
Irrespective of
conditions.
When not 0
Unit
0
Digit
-
Ramp
Function
Inactive
Inactive
Inactive
Active