6 Parameter Settings and Functions
6.2.4

Auto/Manual Control Settings

6.2.4.1
Manual Control Baseline MV.
58
Auto control
: This mode implements control over MV, which is calculated under PID control and
based on SV as the target.
Manual control
: This mode implements control with user-defined MV.
Group
Monitoring Group
Can be used by setting digital input terminal (DI1, DI2) to STOP function.
When switching from auto to manual control you can set the initial MV.
AUTO-MV: When switching modes use auto control MV as the initial manual control.
PRESET-MV: Apply preset MV as the initial MV.
Preceding
Group
Condition
Control
Setting
PID
Group
Parameter
Auto-Manual Control
Auto/manual control switching is not allowed in ON/OFF control
mode.
When the unit is powered on following a power interruption or
shutdown, auto or manual control will be maintained.
When in operation, AT (Auto-tuning) can be switched to manual
control.
When in Stop mode, manual control can be activated.
If an SBA (Sensor Break Alarm) occurred during standard
control, the sensor error MV (Er.MV) is applied. In this state,
switching to manual mode is possible and manual control MV
settings can also be modified.
When the control unit is in operation, it is possible to switch to
manual or auto control mode.
Priority: Manual control > Stop > Open (sensor disconnection)
Parameter
Initial Manual
MV
© Copyright Reserved Autonics Co., Ltd.
Factory
Range
Default
AUTO, MANUAL
AUTO
Factory
Range
Default
AUTO-MV:
AUTO-MV:
PRESET-MV:
Unit
-
Unit
-