GE TRANSFORMER MANAGEMENT RELAY 745 Instruction Manual page 64

Table of Contents

Advertisement

5.2 AUTO-CONFIGURATION
Table 5–1: TRANSFORMER TYPES (SHEET 9 OF 24)
TRANSFORMER
WDG # CONNECTION
TYPE
Y/d150°/d30°
1
2
3
Y/d150°/d150°
1
2
3
5
Y/d150°/d210°
1
2
3
Y/d150°/d330°
1
2
3
5-14
Courtesy of NationalSwitchgear.com
VOLTAGE
PHASE
PHASORS
SHIFT
WYE
150° lag
(gnd 1/2)
DELTA
150° lag
DELTA
120° lag
30° lag
WYE
150° lag
(gnd 1/2)
DELTA
150° lag
DELTA
150° lag
WYE
150° lag
(gnd 1/2)
DELTA
150° lag
DELTA
300° lag
210° lag
WYE
150° lag
(gnd 1/2)
DELTA
150° lag
DELTA
180° lag
330° lag
745 Transformer Management Relay
Table 5–1: TRANSFORMER TYPES (SHEET 10 OF 24)
TRANSFORMER
WDG # CONNECTION
TYPE
Y/d210°/y0°
1
WYE
(gnd 1/2)
2
DELTA
210° lag
3
WYE
(gnd 2/3)
Y/d210°/y180°
1
WYE
(gnd 1/2)
2
DELTA
210° lag
3
WYE
(gnd 2/3)
180° lag
Y/d210°/d30°
1
WYE
(gnd 1/2)
2
DELTA
210° lag
3
DELTA
30° lag
Y/d210°/d150°
1
WYE
(gnd 1/2)
2
DELTA
210° lag
3
DELTA
150° lag
5 SETPOINTS
VOLTAGE
PHASE
PHASORS
SHIFT
210° lag
210° lag
210° lag
30° lag
210° lag
180° lag
210° lag
60° lag
GE Multilin