4 HUMAN INTERFACES
b) 745 FIRMWARE UPGRADES
Prior to downloading new firmware to the 745, it is necessary to save the 745 setpoints to a file (see previous section).
Loading new firmware into the 745's flash memory is accomplished as follows:
1.
Select the Communications > Update Firmware menu item.
2.
A message will appear indicating that the relay firmware will be erased and reprogrammed. Click Yes to proceed with
the firmware upgrade or No to cancel. Again, please ensure that the 745 setpoints have been saved to a file before
proceeding.
3.
Next, 745PC requests the name of the file containing the new firmware. Locate the appropriate file(s) by changing
drives and/or directories until a list of file names appears in the file list box. File names for released 745 firmware have
the following format:
33 D 260 A4 .000
4.
The 745PC software automatically lists file names beginning with 33. Click on the appropriate file name such that it
appears in the File Name box. Click OK to continue.
5.
745PC will provide one final chance to cancel the firmware upgrade before the flash memory is erased. Click Yes to
continue with the firmware upgrade.
6.
745PC will begin to overwrite the flash memory. This process may take several minutes to complete. Upon completion,
the software places the relay back into "normal mode".
7.
Upon successful updating of the 745 firmware, the next step is reloading the saved setpoints back to the 745. See the
following section for details.
GE Multilin
Courtesy of NationalSwitchgear.com
Modification Number (000 = none)
GE Power Management use only
Firmware Revision
Required 745 hardware revision
Product code (33 = 745 Transformer Mgt. Relay)
Figure 4–10: FIRMWARE FILE FORMAT
745 Transformer Management Relay
4.2 745PC SOFTWARE INTERFACE
4
4-11

Advertisement

Table of Contents
loading

Table of Contents