7.4 MODBUS MEMORY MAP
Table 7–6: 745 DATA FORMATS (Sheet 1 of 25)
CODE
APPLICABLE BITS
F1
16 bits
Example: 1234 stored as 1234
F2
16 bits
Example: 123.4 stored as 1234
F3
16 bits
Example: 12.34 stored as 1234
F4
16 bits
Example: –1234 stored as –1234
F5
16 bits
Example: –123.4 stored as –1234
F6
16 bits
Example: –12.34 stored as –1234
F7
32 bits
1st 16 bits
2nd 16 bits
Example: 123456 stored as 123456
F8
32 bits
1st 16 bits
2nd 16 bits
Example: 12345.6 stored as 123456
F9
32 bits
1st 16 bits
2nd 16 bits
Example: 1234.56 stored as 123456
F10
32 bits
1st 16 bits
2nd 16 bits
Example: -123456 stored as -123456
7
F11
32 bits
1st 16 bits
2nd 16 bits
Example: –12345.6 stored as –123456
F12
32 bits
1st 16 bits
2nd 16 bits
Example: –1234.56 stored as –123456
F13
16 bits
0000 0000 0000 0001
0000 0000 0000 0010
0000 0000 0001 1010
F14
16 bits
xxxx 1111 xxxx xxxx
xxxx xxxx 1111 xxxx
xxxx xxxx xxxx 1111
Example: Revision 2.83 stored as 0283 hex
7-48
Courtesy of NationalSwitchgear.com
DEFINITION
UNSIGNED VALUE
UNSIGNED VALUE
1 DECIMAL PLACE
UNSIGNED VALUE
2 DECIMAL PLACES
2's COMPLEMENT SIGNED VALUE
2's COMPLEMENT SIGNED VALUE,
1 DECIMAL PLACE
2's COMPLEMENT SIGNED VALUE,
2 DECIMAL PLACES
UNSIGNED LONG VALUE
high order word of long value
low order word of long value
UNSIGNED LONG VALUE,
1 DECIMAL PLACE
high order word of long value
low order word of long value
UNSIGNED LONG VALUE,
2 DECIMAL PLACES
high order word of long value
low order word of long value
2's COMPLEMENT SIGNED LONG
VALUE
high order word of long value
low order word of long value
2's COMPLEMENT SIGNED LONG
VALUE, 1 DECIMAL PLACE
high order word of long value
low order word of long value
2's COMPLEMENT SIGNED LONG
VALUE, 2 DECIMAL PLACES
high order word of long value
low order word of long value
HARDWARE REVISION
1 = A
2 = B
26 = Z
SOFTWARE REVISION
Major Revision Number
0 to 9 in steps of 1
Minor Revision Number
0 to 9 in steps of 1
Ultra Minor Revision Number
0 to 9 in steps of 1
745 Transformer Management Relay

7.4.2 MEMORY MAP DATA FORMATS

Table 7–6: 745 DATA FORMATS (Sheet 2 of 25)
CODE
APPLICABLE BITS
DEFINITION
F15
16 bits
INSTALLED OPTIONS
xxxx xxxx xxxx xxx1
Windings Per Phase (0 = Two
Windings, 1 = Three Windings)
xxxx xxxx xxxx xx1x
Rating of Winding 1 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxxx x1xx
Rating of Winding 2 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxxx 1xxx
Rating of Winding 3 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxx1 xxxx
Rating of Winding 1/2 Ground Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xx1x xxxx
Rating of Winding 2/3 Ground Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx x1xx xxxx
Control Power (0=LO [20-60 Vdc],
1 = HI [90-300 Vdc/70-265 Vac])
xxxx xxxx 1xxx xxxx
Analog Input/Outputs
(0 = Not Installed, 1 = Installed)
xxxx xxx1 xxxx xxxx
Loss-Of-Life
(0 = Not Installed, 1 = Installed)
xxxx xx1x xxxx xxxx
Restricted Ground Fault
(0 = Not Installed, 1 = Installed)
F16
16 bits
DEMAND INTERVAL/RESPONSE
0000 0000 0000 0000
0 = 5 min
0000 0000 0000 0001
1 = 10 min
0000 0000 0000 0010
2 = 15 min
0000 0000 0000 0011
3 = 20 min
0000 0000 0000 0100
4 = 30 min
0000 0000 0000 0101
5 = 60 min
F17
16 bits
COMMUNICATION HARDWARE
0000 0000 0000 0000
0 = RS485
0000 0000 0000 0001
1 = RS422
F18
16 bits
MAXIMUM DEMAND PHASE
0000 0000 0000 0000
0 = in phase A
0000 0000 0000 0001
1 = in phase B
0000 0000 0000 0010
2 = in phase C
F19
16 bits
COMMAND OPERATION CODE
0000 0000 0000 0000
0000 = NO OPERATION
0000 0000 0000 0001
0001 = REMOTE RESET
0000 0000 0000 0010
0002 = TRIGGER TRACE MEMORY
0000 0000 0000 0011
0003 = CLEAR MAX DEMAND DATA
0000 0000 0000 0100
0004 = CLEAR EVENT RECORDER
0000 0000 0000 0110
0006 = CLEAR TRACE MEMORY
0000 0000 0000 0111
0007 = CLEAR ENERGY DATA
F20
16 bits
RELAY STATUS
xxxx xxxx xxxx xxx1
745 In Service
(0= Not In Service, 1= In Service)
xxxx xxxx xxxx xx1x
Self-Test Error
(0 = No Error, 1 = Error(s))
xxxx xxxx xxxx x1xx
Test Mode (0 = Disabled, 1 = Enabled)
xxxx xxxx xxxx 1xxx
Differential Blocked
(0 = Not Blocked, 1 = Blocked)
xxxx xxxx x1xx xxxx
Local (0 = Off, 1 = On)
xxxx xxxx 1xxx xxxx
Message
(0 = No Diagnostic Messages, 1 =
Active Diagnostic Message(s))
F21
16 bits
SYSTEM STATUS
xxxx xxxx xxxx xxx1
Transformer De-energized
(0 = Energized, 1 = De-energized)
xxxx xxxx xxxx xx1x
Transformer Overload
(0 = Normal, 1 = Overload)
7 COMMUNICATIONS