7.3 MODBUS FUNCTIONS
c) FUNCTION CODE 05H: EXECUTE OPERATION
Modbus implementation:
GE Multilin implementation:
This function code allows the master to perform various operations in the 745. The 2 byte Code Value of FF00h must be
sent after the Operation Code for the operation to be performed.
MESSAGE FORMAT AND EXAMPLE:
Request to perform reset operation in slave device 11.
MASTER QUERY MESSAGE:
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE: high order byte, low order byte
CODE VALUE: high order byte, low order byte
CRC: low order byte, high order byte
SLAVE RESPONSE:
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE: high order byte, low order byte
CODE VALUE: high order byte, low order byte
CRC: low order byte, high order byte
Table 7–2: SUMMARY OF OPERATION CODES FOR FUNCTION CODE 05H
OPERATION
DEFINITION
CODE
0000
NO OPERATION
0001
REMOTE RESET
0002
TRIGGER TRACE
MEMORY
0003
CLEAR MAXIMUM
DEMAND DATA
0004
CLEAR EVENT
RECORDER DATA
0005
CLEAR LOSS-OF-LIFE
7
DATA
0006
CLEAR TRACE
MEMORY
0007
CLEAR ENERGY DATA
7-6
Courtesy of NationalSwitchgear.com
Force Single Coil
Execute Operation
EXAMPLE (HEX):
11
query message for slave 11
05
execute operation
00 01
remote reset
FF 00
perform operation
DF 6A
computed cyclic redundancy check
EXAMPLE (HEX):
11
response message from slave 11
05
execute operation
00 01
remote reset
FF 00
perform operation
DF 6A
computed cyclic redundancy check
DESCRIPTION
Does not do anything.
Performs the same function as the front panel RESET key.
Initiates a waveform capture of trace memory and increments the "Total Number of Trace
Triggers" registers.
Performs the same function as the command in message
DEMAND DATA CLEAR
CLEAR MAX DEMAND DATA
Performs the same function as the command in message
EVENT DATA CLEAR
CLEAR EVENT RECORDER DATA
Performs the same function as the command in message
INSTALLATION
CLEAR LOSS-OF-LIFE DATA
Clears all trace memory buffers and sets the "Total Number of Trace Triggers" register to
zero.
Performs the same function as the command in message
ENERGY DATA CLEAR
CLEAR ENERGY
745 Transformer Management Relay
7 COMMUNICATIONS
A2 METERING
.
A3 EVENT RECORDER
.
S1 745 SETUP
.
A2 METERING
.
DEMAND
ENERGY