5.6 S4 ELEMENTS
MINIMUM OPERATING CURRENT: Enter the minimum value of Winding 1 Phase A current (in units of relay nominal
current) required to allow the overfrequency element to operate.
MINIMUM OPERATING VOLTAGE: Enter the minimum value of voltage (in units of relay nominal voltage) required to
allow the underfrequency element to operate.
OVERFREQUENCY PICKUP: Enter the frequency (in Hz) above which the overfrequency element will pickup and
start the delay timer.
OVERFREQUENCY DELAY: Enter the time that the frequency must remain above the pickup level before the element
operates.
5
5-72
Courtesy of NationalSwitchgear.com
Figure 5–31: OVERFREQUENCY SCHEME LOGIC
745 Transformer Management Relay
5 SETPOINTS
GE Multilin