5 SETPOINTS
TRACE TRIG FLEXLOGIC 01 to 10: The following 10 messages are the parameters of the FlexLogic™ equation for
trace memory triggering as described in the introduction to FlexLogic™.
The Trace Memory default FlexLogic™ is as follows:
TRACE TRIG FLEXLOGIC 01: Any Element PKP
TRACE TRIG FLEXLOGIC 02 to 12: END
PATH: SETPOINTS
S5 OUTPUTS
VIRTUAL OUTPUT 1
[ENTER] for more
Virtual outputs are FlexLogic™ equations whose output (or result) can be used as inputs to other equations. The 745 has
five (5) virtual outputs. One application of these outputs may be to contain a block of logic that is repeated for more than
one output.
This section contains the FlexLogic™ equations to configure Virtual Outputs 1 to 5. The setpoints describe the parameters
of the FlexLogic™ equation for Virtual Output 1(5) as described in the introduction to FlexLogic™.
PATH: SETPOINTS
S5 OUTPUTS
TIMER 1
[ENTER] for more
Protection and monitoring elements already have their own programmable delay timers, where they are required. For addi-
tional flexibility, ten (10) independent timers are available for implementing custom schemes where timers are not available.
For example, a pickup delay timer may be required on a logic input; or, a single delay timer may be required on the output
of a block of logic.
TIMER 1(10) START: Select the FlexLogic™ entry which, when operated or asserted, will start Timer 1(10).
TIMER 1(10) PICKUP DELAY: Enter the delay time during which the start condition for Timer 1(10) must remain oper-
ated or asserted, before the timer will operate.
TIMER 1(10) DROPOUT DELAY: Enter the delay time after which the start condition for Timer 1(10) must remain not
operated or not asserted, before the timer will stop operating.
GE Multilin
Courtesy of NationalSwitchgear.com
VIRTUAL OUTPUTS
VIRTUAL OUTPUT 1(5)
ð
VIRTUAL 1 FLEXLOGIC
ENTER
01: END
ESCAPE
VIRTUAL 1 FLEXLOGIC
ESCAPE
10: END
MESSAGE
TIMERS
TIMER 1(10)
ð
TIMER 1 START:
ENTER
END
ESCAPE
TIMER 1 PICKUP
ESCAPE
DELAY: 0.00 s
MESSAGE
TIMER 1 DROPOUT
ESCAPE
DELAY: 0.00 s
MESSAGE
745 Transformer Management Relay
5.7 S5 OUTPUTS
5.7.6 VIRTUAL OUTPUTS
Range: any FlexLogic™ input or gate
Range: any FlexLogic™ input or gate
Range: any FlexLogic™ input
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
5.7.7 TIMERS
5
5-93