7.4 MODBUS MEMORY MAP
Table 7–5: 745 MEMORY MAP (Sheet 10 of 35)
GROUP
ADDR
(HEX)
HARMONIC
0430
DERATING
0431
0432
0433
043F
FREQUENCY
0440
0441
0442
0444
TAP CHANGER
0445
0446
0448
VOLTAGE
0449
044A
044B
044C
044D
044F
CURRENT
0450
DEMAND
0452
0454
0455
0456
0457
0458
0459
045B
045D
045E
045F
7
0460
0461
0462
0464
0466
0467
0468
0469
046A
046B
046D
046F
0477
AMBIENT
0478
TEMP
0479
047F
LOSS-OF-LIFE
0480
0481
0483
7-22
Courtesy of NationalSwitchgear.com
DESCRIPTION
Winding 1 Harmonic Derating Factor
Winding 2 Harmonic Derating Factor
Winding 3 Harmonic Derating Factor
Reserved
Reserved
System Frequency
Frequency Decay Rate
Reserved
Reserved
Tap Changer Position
Reserved
Reserved
System Line-to-Line Voltage
Volts-per-Hertz
Line-to-Ntrl Voltage - Magnitude
Line-to-Ntrl Voltage - Angle
Reserved
Reserved
Demand Data Last Clear Date (2 registers)
Demand Data Last Clear Time (2 registers)
Winding 1 Phase A Current Demand
Winding 1 Phase B Current Demand
Winding 1 Phase C Current Demand
Winding 1 Max Current Demand
Winding 1 Max Current Demand Phase
Wdg 1 Max Current Demand Date (2 registers)
Wdg 1 Max Current Demand Time (2 registers)
Winding 2 Phase A Current Demand
Winding 2 Phase B Current Demand
Winding 2 Phase C Current Demand
Winding 2 Max Current Demand
Winding 2 Max Current Demand Phase
Wdg 2 Max Current Demand Date (2 registers)
Wdg 2 Max Current Demand Time (2 registers)
Winding 3 Phase A Current Demand
Winding 3 Phase B Current Demand
Winding 3 Phase C Current Demand
Winding 3 Max Current Demand
Winding 3 Max Current Demand Phase
Wdg 3 Max Current Demand Date (2 registers)
Wdg 3 Max Current Demand Time (2 registers)
Reserved
Reserved
Ambient Temperature
Reserved
Reserved
Hottest-spot Winding Temperature
Total Accumulated Loss-of-Life (2 registers)
Aging Factor
745 Transformer Management Relay
RANGE
STEP
UNITS
VALUE
0.00 to 1.00
0.01
---
0.00 to 1.00
0.01
---
0.00 to 1.00
0.01
---
0.00 to 99.99
0.01
Hz
–9.99 to 9.99
0.01
Hz/s
1 to 50
1
---
0.00 to 600.00
0.01
kV
0.00 to 4.00
0.01
V/Hz
0.00 to 600.00
0.01
kV
0 to 359
1
° Lag
---
---
---
---
---
---
---
---
A
---
---
A
---
---
A
---
---
A
---
---
---
---
---
---
---
---
---
---
---
A
---
---
A
---
---
A
---
---
A
---
---
---
---
---
---
---
---
---
---
---
A
---
---
A
---
---
A
---
---
A
---
---
---
---
---
---
---
---
---
–51 to 251
1
°C
–50 to 300
1
°C
0 to 200000
1
hours
0.0 to 2000.0
0.1
-
7 COMMUNICATIONS
FORMAT
FACTORY
CODE
DEFAULT
F3
---
F3
---
F3
---
F3
---
F6
---
F1
---
F3
---
F3
---
F3
---
F1
F23
---
F22
---
F78
---
F78
---
F78
---
F78
0 A
F18
0 = phase A
F23
Jan 01 1996
F22
00:00:00.000
F79
---
F79
---
F79
---
F79
0 A
F18
0 = phase A
F23
Jan 01 1996
F22
00:00:00.000
F80
---
F80
---
F80
---
F80
0 A
F18
0 = phase A
F23
Jan 01 1996
F22
00:00:00.000
F4
---
F4
---
F7
0 hours
F2
-
GE Multilin