6 ACTUAL VALUES
The recorded event displayed for Logic inputs and Virtual Inputs will show the programmed name of the input/output. An
active target display may also be generated as a result of a self-test error. When this occurs, the target message will look
like this:
SELF-TEST ERROR:
<ERROR>
The
part in the above display will be one of the following:
<ERROR>
Logic Power Out
Real-Time Clock
DSP Processor
Not Calibrated
For more detail about these errors, refer to the next section. As well, there is an additional message that may appear as a
target message. It looks like this:
SETPOINTS HAVE NOT
BEEN PROGRAMMED!
This message will be placed in the target message queue whenever
to "Not Programmed". This serves as a warning that the relay has not been programmed for the installation and is therefore
not in the in-service state.
The 745 performs self-diagnostics at initialization (after power-up), and continuously thereafter (in a background task). The
tests ensure that every testable unit of the hardware is functioning correctly.
ANY SELF-TEST ERROR INDICATES A SERIOUS PROBLEM REQUIRING SERVICE.
CAUTION
MAJOR SELF-TEST ERRORS:
Upon detection of a major self-test error, the 745:
disables all protection functionality
turns on the front panel Self-Test Error LED
turns off the front panel In Service LED
de-energizes all output relays, including the Self-Test Relay
indicates the failure by inserting an appropriate message in the target message queue
records the failure in the Event Recorder
MINOR SELF-TEST ERRORS:
Upon detection of a minor self-test error, the 745:
turns on the front panel Self-Test Error LED
de-energizes the Self-Test Relay
indicates the failure by inserting an appropriate message in the target message queue
records the failure in the Event Recorder
GE Multilin
Courtesy of NationalSwitchgear.com
Analog Output
Emulation Software
Bad Xfmr Settings
Flexlogic Eqn
EEPROM Memory
Access Denied
Int Temperature
IRIG-B Signal
745 Transformer Management Relay
6.6 TARGET AND FLASH MESSAGES
S1 745 SETUP
INSTALLATION
6.6.2 SELF-TEST ERRORS
is set
745 SETPOINTS
6
6-19

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRANSFORMER MANAGEMENT RELAY 745 and is the answer not in the manual?

Table of Contents