6 ACTUAL VALUES
6.3A2 METERING
a) MAIN MENU
PATH: ACTUAL VALUES
CURRENT
[ENTER] for more
For each monitored winding, the fundamental frequency magnitude and phase angle of phase A, B, C and ground currents
are recalculated every half-cycle for use in differential and overcurrent protection. From these values, neutral, positive, neg-
ative and zero-sequence as well as differential, restraint and ground differential currents are calculated. These are dis-
played and updated approximately twice a second for readability.
b) WINDING CURRENTS
PATH: ACTUAL VALUES
W1 CURRENT
[ENTER] for more
The fundamental frequency current magnitudes for Winding 1 phases A, B, and C, neutral, and ground are shown. The cur-
rent angle for Phase A is always set to 0° as it is used as reference for all other currents, both measured and derived. The
maximum specified load and average phase current are also shown for the specified winding.
GE Multilin
Courtesy of NationalSwitchgear.com
A2 METERING
CURRENT
ð
W1 CURRENT
ENTER
[ENTER] for more
ESCAPE
W2 CURRENT
ESCAPE
[ENTER] for more
MESSAGE
W3 CURRENT
ESCAPE
[ENTER] for more
MESSAGE
POSITIVE SEQUENCE
ESCAPE
[ENTER] for more
MESSAGE
NEGATIVE SEQUENCE
ESCAPE
[ENTER] for more
MESSAGE
ZERO SEQUENCE
ESCAPE
[ENTER] for more
MESSAGE
DIFFERENTIAL
ESCAPE
[ENTER] for more
MESSAGE
RESTRAINT
ESCAPE
[ENTER] for more
MESSAGE
GND DIFFERENTIAL
ESCAPE
[ENTER] for more
MESSAGE
A2 METERING
CURRENT
W1(3) CURRENT
ð
W1 PHASE A CURRENT:
ENTER
0 A at
0° Lag
ESCAPE
W1 PHASE B CURRENT:
ESCAPE
0 A at
0° Lag
MESSAGE
W1 PHASE C CURRENT:
ESCAPE
0 A at
0° Lag
MESSAGE
W1 NEUTRAL CURRENT:
ESCAPE
0 A at
0° Lag
MESSAGE
W1 GROUND CURRENT:
ESCAPE
0 A at
0° Lag
MESSAGE
WINDING 1 LOADING:
ESCAPE
0% of rated load
MESSAGE
W1 AVERAGE PHASE
ESCAPE
CURRENT:
MESSAGE