7.4 MODBUS MEMORY MAP
Table 7–5: 745 MEMORY MAP (Sheet 30 of 35)
GROUP
ADDR
(HEX)
WINDING 3
2270
NEG SEQ TIME
2271
O/C
2272
2273
2274
2275
2276
2277
↓
227F
WINDING 1
2280
NEG SEQ INST
2281
O/C
2282
2283
2284
2285
↓
228F
WINDING 2
2290
NEG SEQ INST
2291
O/C
2292
2293
2294
2295
↓
229F
WINDING 3
22A0
NEG SEQ INST
22A1
O/C
22A2
22A3
22A4
UNDER
22A5
FREQUENCY
↓
1
22AF
7
22B0
22B1
22B2
22B3
22B4
22B5
22B6
22B7
22B8
↓
22BF
UNDER
22C0
FREQUENCY
22C1
2
22C2
22C3
22C4
22C5
22C6
22C7
7-42
Courtesy of NationalSwitchgear.com
DESCRIPTION
Winding 3 Neg Seq Time O/C Function
Winding 3 Neg Seq Time O/C Target
Winding 3 Neg Seq Time O/C Pickup
Winding 3 Neg Seq Time O/C Shape
Winding 3 Neg Seq Time O/C Multiplier
Winding 3 Neg Seq Time O/C Reset
Winding 3 Neg Seq Time O/C Block
Reserved
↓
Reserved
Winding 1 Neg Seq Inst O/C Function
Winding 1 Neg Seq Inst O/C Target
Winding 1 Neg Seq Inst O/C Pickup
Winding 1 Neg Seq Inst O/C Delay
Winding 1 Neg Seq Inst O/C Block
Reserved
↓
Reserved
Winding 2 Neg Seq Inst O/C Function
Winding 2 Neg Seq Inst O/C Target
Winding 2 Neg Seq Inst O/C Pickup
Winding 2 Neg Seq Inst O/C Delay
Winding 2 Neg Seq Inst O/C Block
Reserved
↓
Reserved
Winding 3 Neg Seq Inst O/C Function
Winding 3 Neg Seq Inst O/C Target
Winding 3 Neg Seq Inst O/C Pickup
Winding 3 Neg Seq Inst O/C Delay
Winding 3 Neg Seq Inst O/C Block
Reserved
↓
Reserved
Underfrequency 1 Function
Underfrequency 1 Target
Underfrequency 1 Minimum Operating Current
Underfrequency 1 Pickup
Underfrequency 1 Delay
Underfrequency 1 Block
Underfrequency 1 Current Sensing
Underfrequency 1 Minimum Operating Voltage
Reserved
↓
Reserved
Underfrequency 2 Function
Underfrequency 2 Target
Underfrequency 2 Minimum Operating Current
Underfrequency 2 Pickup
Underfrequency 2 Delay
Underfrequency 2 Block
Underfrequency 2 Current Sensing
Underfrequency 2 Minimum Operating Voltage
745 Transformer Management Relay
RANGE
STEP
UNITS
VALUE
---
---
---
---
---
---
× CT
0.05 to 20.00
0.01
---
---
---
0.00 to 100.00
0.01
---
---
---
---
---
---
---
↓
↓
↓
---
---
---
---
---
---
× CT
0.05 to 20.00
0.01
0 to 60000
1
ms
---
---
---
↓
↓
↓
---
---
---
---
---
---
× CT
0.05 to 20.00
0.01
0 to 60000
1
ms
---
---
---
↓
↓
↓
---
---
---
---
---
---
× CT
0.05 to 20.00
0.01
0 to 60000
1
ms
---
---
---
↓
↓
↓
---
---
---
---
---
---
× CT
0.05 to 1.00
0.01
45.00 to 59.99
0.01
Hz
0.00 to 600.00
0.01
s
---
---
---
---
---
---
× VT
0.10 to 0.99
0.01
↓
↓
↓
---
---
---
---
---
---
× CT
0.05 to 1.00
0.01
45.00 to 59.99
0.01
Hz
0.00 to 600.00
0.01
s
---
---
---
---
---
---
× VT
0.01 to 0.99
0.01
7 COMMUNICATIONS
FORMAT
FACTORY
CODE
DEFAULT
F30
0 = Disabled
F46
1 = Latched
25 = 0.25 × CT
F3
F36
0 = Ext Inverse
F3
100 = 1.00
F68
1 = Linear
F87
0 = Disabled
↓
↓
F30
0 = Disabled
F46
1 = Latched
1000=10.00 × CT
F3
F1
0 ms
F87
0 = Disabled
↓
↓
F30
0 = Disabled
F46
1 = Latched
1000=10.00 × CT
F3
F1
0 ms
F87
0 = Disabled
↓
↓
F30
0 = Disabled
F46
1 = Latched
1000=10.00 × CT
F3
F1
0 ms
F87
0 = Disabled
↓
↓
F30
0 = Disabled
F46
0 = Self-reset
20 = 0.20 × CT
F3
F3
5900 = 59.0 Hz
F3
100 = 1.00 s
F87
0 = Disabled
F30
1 = Enabled
50 = 0.50 × VT
F3
↓
↓
F30
0 = Disabled
F46
1 = Latched
20 = 0.20 × CT
F3
F3
5880 = 58.8 Hz
F3
10 = 0.10 s
F87
0 = Disabled
F30
1 = Enabled
50 = 0.50 × VT
F3
GE Multilin
Need help?