5.1.3.6. Check of the manual commands

W
!
During this phase of the axis configuration procedure the electronic limit switches
ARNING
are disabled; be careful while using the manual commands.
Set a JOG speed equal to 10% of the maximum speed.
Send the JOG+ command.
Check that the axis is moving in a positive direction.
Send the JOG- command.
Check that the axis is moving in a negative direction.

5.1.3.7. Check of the axis unit of measure

Place the axis in a known mechanical point, pointA, near the minimum limit switch.
Detect the axis ideal value, positionA.
Place the axis in a known mechanical point, pointB, near the maximum limit switch.
Detect the axis ideal value, positionB.
Measure the distance, DISTANCE, between pointA and pointB
Check that the measured distance, DISTANCE, is equal to positionB - positionA
Positive direction
+
Track
lower
limit

5.1.3.8. Calibration of the Absolute Encoder

Place the axis in the mechanical reference point.
Detect the value of the absolute encoder.
Write the detected value in the EAbsQRef parameter.
Save the parameters in Flash.
Take the DGFC card first to the READY status and afterwards to the RUN status.

5.1.3.9. Zero Cycle execution

Send the StartCycle0 command.
Check that the zero cycle has been completed in the right way.
One-axis positioner
Point A
Distance = 300 mm
Position A
-178.34
Distance = Position B - Position A
300 = 121.66 - (-178.34)
—————— Instruction manual ——————
Point B
Quota absolute encoder = 7 864 932
Position B
121.66
Mechanical reference
Track
upper
limit
29