5.5.1 "RESET" Function
The "RESET" function resets stored alarm states, and disables the limit value hysteresis for that in-
stant.
5.5.2 "TEST" function
The "TEST" function simulates a residual current of 1.5 x I
period, the device has the following states:
• Display of the alarm value via the LEDs and the interface.
• The test status can be read out via the interface:
– 0 = no test
– 1 = internal test
– 2 = external test (interface)
• t
and t
on
off
5.5.3 "NFC" Function
The "NFC" function changes the current activation status of the NFC interface, when the T/R but-
ton is pressed and held for a period of 6...10 s.
1 s
3 s
T / R
The NFC interface disables automatically within 5 minutes should it not have been disabled man-
RESET
TEST
ually before.
NFC
1,5 s
1.5 s
5.5.4 "ADDR" function
The "ADDR" function switches the device to address setting mode for the RS-485 address. The LED
measured-value display and the status LED indicate the device's address.
How to enter an address:
1. Press and hold T/R button until status LED flashes green (10...15s).
– After the T/R button is released, the status LED lights RED.
HUNDREDS
2. Set
hold T/R button once (> 2 s) to confirm.
– After the T/R button is released, the status LED lights GREEN.
TENS
3. Set
digit. Press T/R button briefly until the desired value appears. Press and hold
T/R button once (> 2 s) to confirm.
- After the T/R button is released, the status LED lights BLUE.
4. Set UNITS
Press and hold T/R button once (> 2 s) to confirm.
5. To exit the address setting mode, press and hold T/R button once (2 s).
– After the T/R button is released, the status LED lights green.
are set to 0 s for the duration of the test.
6 s
10 s
ADDR
NFC
ON | OFF
Status indication of normal operation with the NFC interface activated
digit. Press T/R button briefly until the desired value appears. Press and
digit. Press T/R button briefly until the desired value appears.
for a period of 5 seconds. During this
Δn
15 s
20 s
PROTECT
ON | OFF
RCMS410_D00424_00_M_XXEN / 09.2022
LINETRAXX® SmartDetect RCMS410
25 s
31
Need help?
Do you have a question about the LINETRAXX SmartDetect RCMS410 and is the answer not in the manual?