2.2.5 Factory settings FAC
There are two ways to carry out a reset:
Factory settings without interface
After restoring the factory settings, all previously changed settings are reset to the state upon
delivery. The settings for the Modbus interface are not reset.
Factory settings with interface
After restoring the factory settings, all previously changed settings including the settings for the
Modbus interface and the device address are reset to the state upon delivery.
i
These settings are configured in Modbus registers 60000...60003, function 4.
2.2.6 Fault memory
The storing of a fault in the memory can be enabled or disabled. When the fault memory is ena-
bled, stored alarms can be reset by performing a reset. The storing of a fault in the memory is fac-
tory-set to disabled.
2.2.7 Monitoring mode
For each channel for this mode either the overcurrent, undercurrent, or window function can be
selected.
• Overcurrent function
Prewarning when measured value > prewarning response value or
main alarm when measured value > residual operating current I
• Undercurrent function
Prewarning when measured value < prewarning response value or
main alarm when measured value < residual operating current I
i
Note that with the undercurrent function the response value of the prewarning is higher
than the residual operating current I
how to proceed.
• Window function An alarm is given when the values fall or rise outside the range
formed by the response value for a prewarning and I
i
The settings for this are configured in Modbus registers 32624...32635.
. See Modbus-register table for an explanation on
Δn
RCMS410_D00424_00_M_XXEN / 09.2022
LINETRAXX® SmartDetect RCMS410
Δn
Δn
.
Δn
13