AI Attributes

This section allows user to configure AI Polled and Events Objects configuration parameters – such as
Analog Input Object 30, 32, and Analog Dead Band Objects - 34.
Table 14: AI Attributes
Object30 Parameters
DNP3 Configuration Parameters
Parameters
AI Attributes
Number of Points for
Object30
Memory Address for
Object30
Description
If Enabled, the AI
parameters get
enabled for
configuration.
If Disabled, the AI
parameters are not
allowed to be
configured.
For CPE115,this
parameter is not
applicable when
configured using
SVC_REQ.
Number of Points
CPU Reference
Memory Type &
Address
June 2020
Valid Values
Value: Enabled/Disabled
Default: Enabled
Value: 1 to 2000
Default: 100
For CPE115 when configured
using SVC_REQ:
Value: 0 to 2000
If set to 0 AI Attributes is not
available.
Value:
Memory Type: %R, %AI, %AQ,
%W
Allocates available reference
Memory ranges
Default: %AI00001
For CPE115 when configured
using SVC_REQ:
Memory Type: 8 - %R, 10 - %AI,
12 - %AQ, 196 - %W,
If set to 0 AI Attributes is not
available.