Point Template Configuration

Table 11: Point Template Configuration

Parameters
Point Template
Configuration
DNP3 Configuration Parameters
Description
DNP3 Outstation supports Point Template
Configuration where a range of points can
have non-default Event Mode and Class
Mask Type. This parameter allows us to
specify the number of point template
configuration that requires non-default
Event Mode and Class Mask Type.
1. If this parameter is configured as 0, No
points in the DNP3 object will
participate in Point Template
Configuration and have default
configured values of Event Mode and
Class Mask type.
2. If it is configured as non-zero, then user
will be provided with Point Template
Configuration Tab with configured
value rows where users can choose
DNP3 Object type and range of Points
with Start and End Indexes for which
the Event Mode and Class Mask Type
can be configured with other than
default values.
Note: A maximum of 100 Point Template
Configurations is supported.
Refer Section 5.8.2.
For CPE115, this parameter is not
applicable when configured using
SVC_REQ.
Section 3
June 2020
Valid Values
Value: 0 to 100
Default: 0