Setting 15
Press "Settings" button to advance to
Setting 15
Press the "Up" or "Down" buttons to
adjust to the desired setpoint. This setting
changes the system/compressor turn-on
temperature above setpoint. Factory
default is 1°F.
Example: Sensor reading = 55°F (13°C)
Setting 15 set to +3°F
System/compressor turns on at 58°F
(14°C)
Setting 16
Press "Settings" button to advance to
Setting 16.
Press the "Up" or "Down" buttons to
adjust to the desired setpoint. This setting
is the minimal allowable temperature
difference between heating and cooling
setpoints. Maximum is 5°F (3°C),
minimum is 1°F (1°C). Factory default is
2°F (1°C).
Setting 17
Press "Settings" button to advance to
Setting 17.
Press the "Up" or "Down" buttons to
adjust to the desired setpoint. This setting
disables or enables the Condensate switch.
0 (zero) is disabled, 1 is enabled. Factory
default is 0.
Settings 18 & 19
Reserved for additional fields.
Setting 20
System setting. DO NOT CHANGE.