Sub-Fc 65 (0X41): Set The Time Interval In The Sequential Mode - ICP DAS USA IR-310-RM User Manual

Ir controlled 10-ch high power relay module
Table of Contents

Advertisement

ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru

5.4.16 Sub-FC 65 (0x41): Set the time interval in the sequential mode

The time interval is the gap time between adjacent relays during forward sequential
ON and backward sequential OFF.
‧Request
Byte order
Description
00
Address
01
FC
02
Sub-FC
03
Time interval
byte0 (LSB)
04
Time interval
byte1 (MSB)
05
Reserved
06
Reserved
‧Response
Byte order
Description
00
Address
01
FC
02
Sub-FC
03
Setting result
Note:
1. The range of the "Time interval" is 0 ~ 65535 ms. (0x0000 ~ 0xFFFF)
IR-310-RM, IR Controlled 10-ch High Power Relay Module (Ver. 1.1, Jul/02/2013) 49
Size
Value
1 Byte
1 ~ 247
1 Byte
0x64
1 Byte
0x41
1 Byte
0x00~0xFF. (low byte)
1 Byte
0x00~0xFF. (high byte)
1 Byte
0x00
1 Byte
0x00
Size
Value
1 Byte
1 ~ 247
1 Byte
0x64
1 Byte
0x41
1 Byte
0=>OK, 0xFF=>error