3.10 Installing a condensate neutralizer

If discharging condensate into building drain piping materials that are subject to corrosion, use a
neutralization package.
Caution
After installing a condensate neutralization package, the pH of the condensate discharge
must be measured on a regular schedule to ensure the neutralizing agent is active and
effective.
Danger
The water in the condensate neutralizer can cause severe burns to the skin. Wear
protective gloves and eye wear when servicing the condensate neutralizer.
Flue gas exhaust: condensate, and potentially rain water, flow back from the venting system.
Air intake piping: Warning - Risk of damage to appliance. Ensure that rain water is
prevented from entering.
Condensate water line: Warning - Risk of damage to appliance. All condensate discharge
lines, including neutralization tank inlet, must be at a lower elevation than the condensate
water line of the appliance.
3.10 Installing a condensate neutralizer
41