1
To remove the condensate
retainer, undo the two wing
nuts. Note the orientation of the
drain hose.
3
Unscrew the union cap at the base
of the trap, and empty and flush the
trap with water.
Section: Service and maintenance
2
Loosen the upper union nut, and
slide the condensate trap off the
boiler drain outlet.
4
Replace the union cap and gasket and
hand-tighten to prevent leakage, and fill
the condensate trap with water.
90