8.3.3 Miscellaneous issues

Issue
Diagnosis
Fumes and
Improperly installed
High
condensate trap
Humidity
Leak in vent piping
Flue gas leak within
boiler
'Ghost' call
Triac or 'Power-
for heat.
robbing' thermostat
sending current to
boiler.
Error: Water
Boiler is in 1-hour
High Limit /
safety lockout.
Low Water
Cutoff won't
clear.
DHW taking
Sensor may be under-
too long to
reading actual water
heat.
temp.
Boiler output
Possible flow issue:
not
check for 35 or 40 °F
modulating
temperature
up to
difference between
maximum
boiler supply and
despite
return water
target not
temperatures (evokes
being
electronic fence).
reached.
Primary
Wiring not complete.
Pump runs
but load
pumps do
not.
Miscellaneous issues
Refer to installation/operation instructions.
Inspect using soap solution.
Visually inspect all mechanical connections.
Remove Therm. connections from boiler to confirm that
stray voltage, or current induced in thermostat wiring, is
source of nuisance signal. Replace the Power Robbing
thermostat, isolate the thermostat with a relay or install a
properly sized resistor (consult the thermostat
manufacturer first then IBC for instructions).
For instructions on clearing errors, see the V10
Touchscreen Controller manual.
Check sensor engagement; note well is 15 cm / almost 6
inches deep and sensor must be fully set to back. Check
programmed settings boiler temp set too close to the
required DHW temperature.
Confirm that primary pump is able to overcome head
loss of boiler and primary loop piping at the required flow
rate.
Supply power to the PV/L and PV/N terminals from the
incoming power supply to the boiler. (Factory wired on
boilers with a factory installed touchscreen controller)
102
Section: Troubleshooting
Fix