The bottom line of the touchscreen displays the boiler's error status. The following colors represent
the boiler's operating status:
Green – Normal
Yellow – Warning
Red – Alarm
The text inside the bar will indicate the specific warning or alarm. If there is more than one alarm
present the text will scroll slowly through all current alarm conditions. Besides the errors listed below,
see also
Miscellaneous touchscreen controller errors on page

8.2.1 Maximum ignition trials error

Issue
Error – Ignition Failure after 3
tries boiler has failed to ignite on
3 successive attempts. Boiler is
in lockout for 1 hour, then
repeats 3-try sequence. Consult
service technician if error
recurs.

8.2.2 Hi Limit cut-off temperature error

Issue
Error – Water High-Limit
Exceeded
Maximum Ignition Trials Error
Diagnosis
No spark when igniting.
Ignition probe/flame
sensor disconnected.
Manual gas shutoff is
closed or gas line not fully
purged.
Gap between ignition
probe rods is too large or
too small.
Boiler ignites, but shuts
off at the end of the
ignition trial. Improperly
grounded pressure
vessel/burner or
unserviceable ignition
lead or spark module.
Hi Limit cutoff temperature Error
Diagnosis
Water temperature exceeds
hi-limit. Boiler is in hard lockout
mode.
97
8.2.1 Maximum ignition trials error
98.
Fix
Check that ignition lead is secure
at the control module and at the
probe.
Check for gas flow. Open manual
gas shutoff and reset boiler.
Adjust ignition probe rod gap
between ⅛ and 3/16th inch (3.2-
4.7 mm).
Ensure the pressure vessel is
grounded. Check the ignition
probe/flame sensor is electrically
isolated from the vessel, and its
ceramic insulator is intact.
Replace ignition lead Replace
spark module.
Fix
Refer to the V10 Touchscreen
Controller manual for
information on resetting a
boiler after a hi-limit
temperature lockout.