intake piping.
Condensate water line.
Warning: Risk of damage to appliance. All condensate discharge lines must be at a lower
elevation than the condensate water line of the appliance.
Affix hose to plastic piping
Factory-supplied condensate trap
Confirm slope. Condensate hose and drain piping to slope toward drain and be secured to
prevent accidental disassembly .
To drain. Drain materials subject to corrosion must be protected by acid neutralization.
Condensate drainage: Free flow of condensate from venting systems and pressure vessel
must be maintained at all times. Trap and condensate drain piping must be accessible to
allow regular inspection and cleaning.

3.10 Installing a condensate neutralizer

If discharging condensate into building drain piping materials that are subject to corrosion, use a
neutralization package.
Caution
After installing a condensate neutralization package, the pH of the condensate
discharge must be measured on a regular schedule to ensure the neutralizing agent is
active and effective.
Danger
The water in the condensate neutralizer can cause severe burns to the skin. Wear
protective gloves and eye wear when servicing the condensate neutralizer.
40