Section: Installation
Figure 21
Sidewall multi-vent terminations, side-by-side option
Sidewall direct vent with stainless sidewall terminal must be terminated as follows:
The Stainless Sidewall Terminal (SST) 3 inch (IBC kit P-257) is approved for use with
this appliance.
Install the SST to comply with the minimum vent clearances listed in
Table 7
.
Install the SST with the vent and intake pipes horizontally beside each other or vertically
with the vent pipe on top. The vent pipe cannot be installed below the intake. The vent
cap must be installed with the openings directed up and down (see
Figure
22), and not
side to side.
34