Fan - IBC SL Series Installation & Operating Manual

Commercial condensing boiler
Table of Contents

Advertisement

Temp. °F/°C
0 / -18
5 / -15
10 / -12
15 / -9
20 / -7
25 / -4
30 / -1
35 / 2
40 / 4
45 / 7
50 / 10
55 / 13
60 / 16
65 / 18
70 / 21
75 / 24
80 / 27
85 / 29
90 / 35
95 / 35
Table 13
Temperature sensor resistance values - 10K ohms

8.1.2 Fan

Operating power is provided by means of a separate 120 VAC connector (white/black/green).
Control of the fan is provided via a four lead connector. This connector feeds a PWM control
signal (black wire) from the controller and provides a tachometer signal (white wire) back from the
fan. Unplugging the control connector will cause the fan to go to high speed and trigger a
"Blocked Vent Error" within 6 seconds if the boiler is operating.
Resist.
Temp. °F/°C
Ω – Ohm
85,362
72,918
62,465
53,658
42,218
39,913
34,558
29,996
26,099
22,763
19,900
17,436
15,311
13,474
11,883
10,501
9,299
8,250
7,334
6,532
94
Section: Troubleshooting
Ω – Ohm
100 / 38
105 / 41
110 / 43
115 / 46
120 / 49
125 / 52
130 / 54
135 / 57
140 / 60
145 / 63
150 / 66
155 / 68
160 / 71
165 / 74
170 / 77
175 / 79
180 / 82
185 / 85
190 / 88
195 / 91
Resist.
5,828
5,210
4,665
4,184
3,760
3,383
3,050
2,754
2,490
2,255
2,045
1,857
1,689
1,538
1,403
1,281
1,172
1,073
983
903