Page 1
• If you cannot reach your gas supplier, call the fire department. • Installation and service must be performed by a qualified installer, service agency or the gas supplier. This Manual is also available in French - contact IBC or visit our web site www.ibcboiler.com www.ibcboiler.com...
Page 2
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SAFETY CONSIDERATIONS Installation, start-up and servicing of IBC boilers must be done with due care and WARNING attention, and should only be performed by competent, qualified, licensed and trained heating technicians.
Page 7
SL 20-115 G2 MODULATING GAS BOILER SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS The Installer must carefully read this manual to ensure that all installation details can be adhered to. Special attention is to be paid to clearances and access, vent travel and termination, gas supply, condensate removal and combustion air supply.
Page 8
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS THIS PAGE IS INTENTIONALLY LEFT BLANK INSTALLATION AND OPERATION INSTRUCTIONS...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 1.0 INSTALLATION 1.1 GENERAL SL Series gas-fired modulating boilers are low pressure, fully condensing units having variable input ranges (see specification chart - inside, front cover). Approved as “Category IV”...
Page 10
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 2: Dimensions / Connections for SL 20-160 G3 - Front view, side view, top view and bottom view Figure 3: Dimensions / Connections for SL 30-199 G3 - Front view, side view, top view and bottom view...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS DISTANCE FROM RECOMMENDED DISTANCE WARNING SURFACE COMBUSTIBLE FOR INSTALLATION AND...
Page 13
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS system is likely to be too large for the proper venting of the appliances that remain WARNING connected to it.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 1.4.1 Applications All SL series boilers are approved with alternative venting options: either 2-pipe Direct Vent or Vent pipe with Indoor Air, offering flexibility to meet the specific requirements of the installation.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS b) For Rooftop Direct Vent systems: WARNING • Rooftop, two pipe, direct vent configurations, including typical clearance requirements, Condensate can cause corrosion are shown in Figure 6.
Page 18
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS • Clearance to a mechanical air supply inlet: - 6’ (1.82m) (USA - 3’ (0.91m) above if within 10’...
Page 19
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS b) Sidewall vent termination for indoor combustion air applications shall be as...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Combustion air piping - if used - is inserted directly into the 3” female stainless steel fitting on the top, right side of the boiler and run horizontally or vertically to the outdoors.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 1.4.9 Combustion Air Filtration NOTE If combustion air contamination from ingested particulate matter is a concern in any Combustion fan blockages installation, an optional air intake filter may be installed.
The extremely low pressure drop through the SL Series heat exchanger allows many options not available in other designs. In short – IBC has built a boiler that will allow you to pipe the system the way you prefer, rather than try and dictate your piping practices from boiler to radiator.
Page 29
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS WARNING During operation, the relief valve may discharge large amounts of steam and/or hot water.
Page 30
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 28: Relief piping with single side piping connections Figure 29: Relief piping with dual side connections 1-22 INSTALLATION AND OPERATION INSTRUCTIONS...
Page 31
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS System piping is connected to the boiler using the 1” NPT Male threaded fittings on the right or left side connection ports. Unions and gate or ball valves at the boilers supply and return water connections are recommended to simplify servicing.
Page 32
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS The SL series modulating boilers are designed to supply three different heating loads with WARNING temperatures within the range 34°F to 180°F - to meet three separately piped loads. Use closely spaced tees to connect each pumped “load”...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 31: Important primary-secondary piping details with closely-spaced tees WARNING The SL series modulating boilers offer exceptional matching of heat generation to radiation. The low minimum firing is better suited to low thermal loads presented in a Do not use automotive-type typical multi-zoned radiation system.
Page 34
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 32: One-temperature space heating piping concept - tees on secondary piping Figure 33: Typical one-temperature space heating piping concept 1-26 INSTALLATION AND OPERATION INSTRUCTIONS...
Page 35
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS NOTE Load Combining is now available to operate 2 compatible water temperature loads at the same time.
Page 36
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS NOTE The piping drawings in this manual are simple schematic guides to a successful installation.
Page 37
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Parallel load piping - Benefits and installation rules Compared with the Primary/Secondary approach, the design below saves one pump. Lost is the simplicity of constant head and flow at the boiler.
Page 38
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Check valves or thermal traps should be used to isolate both the supply and return piping NOTE for each load - to avoid thermal siphoning and reverse flow.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS NOTE It is essential to check gas supply pressure to each boiler with a manometer or other high-quality precision measuring device. Pressure should be monitored before...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Gas piping must have a sediment trap ahead of the boiler’s gas valve (see Figure 44). A manual shutoff valve must be located outside the boiler, in accordance with local codes/ standards.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS The boiler (primary) pump is connected to the White/Yellow pair labeled Primary Pump. NOTE This lead is factory wired to the controller (and its 120 VAC supply) at the upper right backside of the controller board.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 1.8.5 Other Wiring Other optional low voltage connections to the control board include: • Two auxiliary interlocks - for external safety devices as may be required by some jurisdictions, such as a low water cut-off or a low gas pressure cut-out (for off-grid propane).
Page 43
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 43: Electrical Wiring Connections (full page ladder diagram at back of this manual)
Page 44
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS THIS PAGE IS INTENTIONALLY LEFT BLANK 1-36 INSTALLATION AND OPERATION INSTRUCTIONS...
Load Combining – simultaneous operation of 2 similar water temperature loads • The control can manage and/or operate in a network of up to 24 IBC VFC or SL boilers Some of the new features available in the touch screen control include: •...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Operational and historical data may be accessed at any time using the System Status and Load Profiles sections of the control. Error logs are available in the Diagnostics section and the controller is capable of recording any or all errors since original power-up complete with the date and time of the error.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 3.2 PRIOR TO START-UP WARNING 3.2.1 Pre-Ignition Checks Fill trap with water before boiler is first fired to prevent exhaust fumes Ensure venting system is complete and seal tested. Confirm any common venting from entering room.
Page 49
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS To verify the proper operation of the gas valve in the field, the following procedure must DANGER be carried out by a qualified technician (see Figure 44 for details of the gas valve and pressure system ).
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 3.4 FUEL CONVERSION DANGER The SL modulating boilers are factory fire-tested to operate with natural gas, or propane Operating any IBC boiler using as ordered. The rating plate will be marked to indicate which fuel the particular boiler a fuel other than the fuel listed has been set up with.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Figure 44: Gas Valve and Pressure Reference System 3.4.1 Gaining access to the combustion chamber Remove the fan and gas valve assembly. See “Fan and gas valve removal instructions”...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Re-assembly NOTE Inspect the refractory for cracks, degradation and flatness. If in doubt, replace with a The safety warning regarding new one. burner refractory on page 4-2 of If installing a new refractory, first place it onto the lid, aligning it at the igniter hole, this manual must be observed.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS cracking. 12. Place the lid with the burner attached, on a clean dry area. 13. With a permanent marker or equivalent, make an alignment mark on the refractory, lining it up with the same mark made earlier between the lid and heat exchanger.
Page 54
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS THIS PAGE IS INTENTIONALLY LEFT BLANK INSTALLATION AND OPERATION INSTRUCTIONS...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 4.1.7 Pump CAUTION Check that the pump is on in normal operation and that the water Δ°T is reasonable for a The heat exchanger has a small given firing rate (e.g.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 4.1.13 Relief Valve - Maintenance and Testing CAUTION The relief valve manufacturer requires that under normal operating conditions a “try Before testing the relief valve, lever test”...
SL 20-115 G2 MODULATING GAS BOILER SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 4.2.1 Fan and gas valve removal instructions DANGER Turn off the power and the gas supply to the boiler.
Page 60
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS THIS PAGE IS INTENTIONALLY LEFT BLANK INSTALLATION AND OPERATION INSTRUCTIONS...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 5.2 ELECTRONIC COMPONENTS This section details the method for troubleshooting the non-standard electronic components on the boiler including the electronic differential air pressure sensor and the temperature sensors.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 5.2.2 Fan The fan is controlled by the SIM , and powered via one cable. 5.2.3 Water Pressure Sensor The water pressure sensor ensures that there is adequate pressure in the heating system for safe operation.
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS The SIM’s two status LEDs indicate the operating status as shown in the table below. Status Indicators DESCRIPTION, LED STATUS LED 1 LED 2 STATE...
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Tap the SIM Module button. Tap the LWCO Test button. Disconnect the yellow wire from the LWCO function. A message on the screen indicates that the boiler is in lockout mode.
SL 20-115 G2 MODULATING GAS BOILER SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS 5.3 TROUBLESHOOTING 5.3.1 Using Control Module Errors Displayed WARNING Never attempt to repair the control module (circuit board). If the control module is defective, replace it immediately.
Page 67
SL 20-115 G2 MODULATING GAS BOILER SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS SYMPTOM DIAGNOSIS REMEDY TEMPERATURE SENSOR Current outlet • Check water flow. ERROR temperature exceeds operating limit. Touch Screen Message: Defective or •...
Page 81
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS Better SL 14-115G3, SL 20-160G3, SL 20-199G3 INTERNAL WIRING DIAGRAM Boilers P303 brown white NRG130 Combustion green black P 101 green orange brown blue Valve...
INSTALLATION & COMMISSIONING REPORT Boiler Details: Model Number _____________________ Serial Number ______________________________________________ Date of Installation ______________ Address of installation __________________________________________ _____________________________________________________________________________________________ User contact information _______________________________________________________________________ Installer Information Company ___________________________________________________________________ Address ______________________________________________________________________________________ Phone/Fax/E mail ______________________________________________________________________________ Fuel Natural Gas Propane Gas Supply Pressure (high fire) _______ Inches w.c. Measured Rate of Input (high fire) ____________ Btu/hr Installation instructions have been followed and completed (Section 1 of Installation and Operating Instructions).
Page 88
• This boiler is part of a modular or multiple boiler system having a total input 300,000 BTU/hr or greater. • This boiler is equipped with a tankless coil (not applicable to IBC’s SL boilers). US installers should contact IBC for any further information required.
REVISION HISTORY R1 (MARCH 2017) Initial release R2 (APRIL 2017) Revision of Figures 33 and 34. Corrections to text (Specifications table and part numbers). R3 (MAY 2017) Corrections to tables and part numbers. R4 (July 2017) Inclusion of information relating to the SL 30-199 G3 boiler. R5 (September 2017) Inclusion of information relating to the SL 10-85 G3 boiler.