Cycling Issues - IBC SL Series Installation & Operating Manual

Commercial condensing boiler
Table of Contents

Advertisement

8.3.4 Cycling issues

Issue
Diagnosis
Rapid
Improper values entered via
Cycling
keypad.
Excess condensate in
venting.
Obstruction in condensate
trap.
Improper vent length or
improper slope to vent.
Incorrect settings or
defective thermostat.
Air in system or marginal
water flow.
Slow combustion air blower. Check that CO
Dirty burner/heat
exchanger.
Low water flow due to
improper piping.
Low water flow due to
undersized pump.
Low water flow due to
restrictions in water pipe.
Low radiation.
Appliance over-fired.
Appliance Oversized.
Improperly set or defective
controls.
Cycling issues
Check load maximum temps are above target temps, by ½
of the selected boiler differential. Ensure boiler differential
is OK (16 - 30 °F is generally adequate)
Check venting slopes on horizontal runs. Look for sags.
Inspect and clean condensate trap.
Check venting. Compare vent length and diameter.
Check operation. Refer to manufacturer's instructions.
Check setting with ammeter.
Bleed/purge system as required. Confirm adequate pump
size and temp rise in the heat exchanger.
level is within specification.
2
Check pressure drop.
Refer to recommended piping for the respective boiler
model.
Check manufacturer's rating charts/check temperature
differential across heat exchanger.
Check temperature differential across zone/heat
exchanger.
Check actual amount of radiation per zone and refer to
manufacturer's rating tables.
Clock gas meter/check gas pressure with manometer/
check CO
level.
2
Check load calculation vs. minimum boiler output.
Check operation with ohmmeter/voltmeter.
103
8.3.4 Cycling issues
Fix