Cleaning The Condensate Trap - IBC SL Series Installation & Operating Manual

Commercial condensing boiler
Table of Contents

Advertisement

7.4 Cleaning the condensate trap

Warning
If condensate neutralization is used, check the pH level of condensate before and after
neutralization to verify effectiveness and ensure that the discharge has neutral pH levels.
Never operate the boiler unless the trap is filled with water. Failure to comply will result in
severe personal injury or death.
7.4 Cleaning the condensate trap
Condensate traps should
be checked every year,
cleaned and refilled as
necessary. Before
cleaning the condensate
trap, you must turn off the
power to the boiler, and
allow it to cool down.
Important: Installers or
service contractors should
ensure that the end user is
instructed on cleaning and
refilling the trap.
89
Warning
Before
replacing the
condensate
trap, turn off the
power to the
boiler and allow
to cool down.