Festo CPX-AP-A-8DO-M12-5P Operating Instructions Manual page 10

Digital output module
Table of Contents

Advertisement

Diagnostics and fault clearance
ID hex (dec)
Message
02 | 01 | 0106
Switch off load supply
(33620230)
PL 24 V DC
02 | 01 | 013F
Overvoltage in load
(33620287)
supply PL 24 V DC
08 | 01 | 0124
Communication to AP
(134283556)
master interrupted
08 | 01 | 0130
Output process data
(134283568)
watchdog of the AP
module expired
08 | 01 | 0131
Input process data
(134283569)
watchdog of the AP
module expired
08 | 01 | 01A2
Device in emergency
(134283682)
operation system
state
10
Description
A switch-off of the load supply PL was detected. The cause
can be a deliberate shutdown by the emergency stop.
– Check if the emergency stop was activated.
Remedy
– Check load supply PL.
Diagnos-
Information
tics
status
Overvoltage in load supply PL 24 V DC
– Check load supply PL.
Remedy
Diagnos-
Error
tics
status
Diagnostics status
– Restart AP Master.
Remedy
– Check communication AP connecting cable.
Diagnos-
Error
tics
status
Output process data watchdog of the AP module expired
– Restart AP system.
Remedy
– Check the cable.
Diagnos-
Error
tics
status
Input process data watchdog of the AP module expired
– Restart AP system.
Remedy
– Check the cable.
Diagnos-
Error
tics
status
System initialisation (module detection) has failed. The
system is in maintenance mode. There is no I/O function
available.
Festo — CPX-AP-A-8DO-M12-5P — 2022-07

Advertisement

Table of Contents
loading

Table of Contents