UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5.6 Testing Batteries
5.6.1 Forced Equalized Charging Test
Context
Before a forced equalized charging test, ensure that:
Procedure
Step 1 On the main screen of the LCD, tap System Info. Tap
displayed.
Step 2 (Optional) If no user is logged in, enter a user name and a password, and then tap
Step 3 On the Maintenance screen, tap Battery Maint., as shown in
Figure 5-24 Maintenance screen
Step 4 Tap Start next to Forced Equalized Charging to start a forced equalized charging test, as
shown in
Issue 02 (2017-02-25)
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
For details about default user names, preset passwords, and user rights, see
If an incorrect password is entered three consecutive times, the account will be logged out for 5
minutes.
Figure
5-25.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
. The Maintenance screen is
Table
4-5.
Figure
5-24.
.
222