Huawei UPS5000-E User Manual page 100

50 kva power modules
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Context
Procedure
Step 1 (Optional) Determine the installation position for the cable entry cabinet, and draw mounting
holes in the installation position based on drawings.
Figure 3-52 Mounting holes for the cable entry cabinet
Step 2 Remove the right and rear covers from the UPS cabinet, and remove the front and rear covers
from the cable entry cabinet. Put away the removed screws and covers.
Step 3 Adjust the anchor bolts of the cable entry cabinet to make it flush with the UPS cabinet.
Issue 02 (2017-02-25)
Route cables for the UPS from inside out and from bottom up.
A cable entry cabinet can be placed only on the right of the UPS cabinet.
In the scenarios where holes are drilled or covers are removed for routing cables, use
firestop putty to fill in the gap between the cables and the cabinet after routing cables and
checking cable connections.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation
91