Recharge Requirements For Batteries With Low Soc - Huawei SmartLi-ESM-24020P1 Quick Manual

Table of Contents

Advertisement

SmartLi-ESM-24020P1
Quick Guide
Figure 2-17 Switching to another device
Step 2 Press and hold the activate button on the front panel of each battery module for
5s to 10s. After the running indicator and SOC indicator turn off, release the
activate button.
----End

2.5 Recharge Requirements for Batteries with Low SOC

Charge batteries if the battery system is powered off for commissioning or
batteries are discharged. Otherwise, batteries may be damaged due to
overdischarge.
Battery overdischarge and damage may occur if batteries with low SOC are stored.
Batteries should be recharged in a timely manner.
Storing batteries with low SOC may occur in the scenarios including but not
limited to the following:
Issue 03 (2022-12-30)
NO TE
● Record the battery SOC to determine the battery charging interval during storage.
● Tap ... in the upper right corner of the Overview screen to view the SOC of other
battery modules.
CA UTION
CA UTION
Batteries cannot be charged after commissioning and power-off.
Batteries are not charged in time after commissioning and power-off.
After batteries are discharged, the power grid does not supply power for a
long time and batteries cannot be charged in time.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On Commissioning