UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 4-46 Battery Param. screen 4
Item
Backup time warning
Remain. cap. warning
Dis. cur. 0.1C EOD
(V/cell), Dis. cur. 0.3C
EOD (V/cell), Dis. cur.
0.5C EOD (V/cell), and
Dis. cur. 1.0C EOD
(V/cell)
Figure 4-47 Battery Param. screen 5
Issue 02 (2017-02-25)
Description
An alarm is generated if this parameter is set to Enable and
the backup time is lower than the warning threshold.
An alarm is generated if this parameter is set to Enable and
the remaining capacity is lower than the warning threshold.
By default, 0.1C EOD (V/cell) is set to 1.80, 0.3C EOD
(V/cell) to 1.75, 0.5C EOD (V/cell) to 1.67, and 1.0C EOD
(V/cell) to 1.60. These values are calculated in real time based
on the discharge currents.