Huawei UPS5000-E User Manual page 153

50 kva power modules
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Item
IP address
Subnet mask
Gateway
NAT mapping
RS485 com. baud
rate
Figure 4-32 Communication screen 2
Item
RS485
com.
address
Parity
mode
Stop bit
Batt. temp.
Issue 02 (2017-02-25)
Description
Set an Ethernet IP address that ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.10.
NOTICE
Ensure that the UPS IP address is unique on the network segment. Otherwise,
the WebUI display function may not function properly.
Set an Ethernet subnet mask that ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255.
The default value is 192.168.0.1.
NAT means network address translation. If it is set to Disable, an
internal IP address cannot be accessed from the Internet.
Baud rate depends on the network management conditions.
Description
Set an address that ranges from 1 to 254 for this port.
Verify the validity of RS485 communication characters. When a device
node adopts RS485 communication, ensure that the parity modes for the
device nodes are set to the same mode. Available parity modes include
None, Odd, and Even.
Stop bit in the Modbus communication frame format. When the UPS is
connected over the serial port Modbus, set this parameter based on the
frame format that the upstream device Modbus supports.
A maximum of four battery temperature sensors can be cascaded.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
144