Huawei UPS5000-E User Manual page 35

50 kva power modules
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 2-14 Bypass module
(1) Positioning lock
(5) Fault indicator
(9) Crowbar
Functions
The bypass module supplies power in the following cases:
If the UPS is set to ECO mode and the bypass voltage is within the specified range, the UPS
works in bypass mode.
If the power module overload times out, the UPS transfers to bypass mode.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.
Specifications
Issue 02 (2017-02-25)
(2) Cold start button
(6) Ready switch
Dimensions (H x W x D): 130 mm x 420 mm x 500 mm
Weight
200 kVA: 19 kg
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(3) Run indicator
(4) Alarm indicator
(7) Signal port
(8) Input and output ports
2 Overview
26