Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Alarm
ID
(Alarm
ID-Caus
e ID)
0334
0337
0338
0341
0342
0343
0340
0335
0594-1
Issue 02 (2017-02-25)
Alarm
Severit
Name
y
system
BSC slave
system
PDC
Critical
bypass
input
breaker
open
PDC output
Critical
breaker
open
PDC
Minor
Maint.
breaker
closed
Mains
Critical
input
breaker
open
BPM input
Critical
breaker
open
Maint.
Minor
breaker
closed
Generator
Warning
connected
Insufficient
Minor
redundant
racks
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
BSC slave
The running status is displayed. No
system.
further measures are required.
The bypass
The running status is displayed. No
input circuit
further measures are required.
breaker on
the PDC is
OFF.
1. Check that all UPS output
The output
circuit breakers are ON.
circuit
breaker on
2. On the LCD, check that PDC
the PDC is
output breaker open alarm has
OFF.
disappeared. If the alarm
persists, tap the Clear Fault
button to clear the alarm.
The
The running status is displayed. No
maintenance
further measures are required.
circuit
breaker on
the PDC is
ON.
The mains
The running status is displayed. No
input circuit
further measures are required.
breaker is
OFF.
The bypass
The running status is displayed. No
input circuit
further measures are required.
breaker is
OFF.
The
The running status is displayed. No
maintenance
further measures are required.
circuit
breaker is
ON.
The generator
The running status is displayed. No
is connected.
further measures are required.
1. Reduce the load.
The load
is
2. Decrease the configured number
excessive.
of redundant racks.
The
configure
d number
C Alarm List
286