Testing Batteries; Lead-Acid Battery Test - Huawei UPS5000-E-200K-SM User Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
No.
Check Item
6
Shallow
discharge test
(recommende
d)
7
Capacity test
(recommende
d)

6.3 Testing Batteries

6.3.1 Lead-Acid Battery Test

Issue 17 (2023-07-10)
Acceptance Criteria
During the shallow
discharge test, no fault or
alarm is displayed on the
UPS LCD.
During the capacity test,
no fault or alarm is
displayed on the UPS LCD.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method
● Check method: Perform
a shallow discharge
test and check the
alarm information on
the UPS LCD. Measure
and record the voltage
of a single battery
during shallow
discharge.
● Troubleshooting: View
the alarm information
on the LCD of the UPS
and handle the alarm.
Send the recorded
battery voltage to the
battery manufacturer
to determine whether
the battery is normal.
● Check method: Perform
a capacity test and
check the alarm
information on the UPS
LCD.
● Troubleshooting: View
the alarm information
on the LCD of the UPS
and handle the alarm.
6 Routine Maintenance
Check
Interval
Quarterly
Yearly
205