Huawei UPS5000-E User Manual page 290

50 kva power modules
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Alarm
ID
(Alarm
ID-Caus
e ID)
0043-1
0043-2
0043-3
0043-4
0047-1
0060-4
0061-2
Issue 02 (2017-02-25)
Alarm
Severit
Name
y
Fan
Critical
abnormal
Not ready
Critical
Inverter
Critical
abnormal
Inverter
Minor
alarm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
for the
power
module is
obstructed
.
The fan
Replace the faulty power module.
for the
power
module is
abnormal.
The fan
monitorin
g cable
for the
power
module is
not
working
properly.
The fan is
Check the fan or replace the bypass
faulty.
module.
1. Replace the fan.
The fan is
faulty.
2. Check the fan monitoring cable.
The fan
monitorin
g cable is
faulty.
The ready
Close the ready switch.
switch is
OFF.
1. Check load cable distributions.
A load
short-circ
2. If load cable distributions are
uit occurs.
normal, replace the power
module.
A short
circuit
occurs
inside the
module.
(This fault
seldom
occurs.)
1. Rectify the fault and check
The I2C
whether the alarm is cleared.
bus is not
2. If the alarm is generated again,
C Alarm List
281