Huawei UPS5000-E User Manual page 286

50 kva power modules
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Alarm
ID
(Alarm
ID-Caus
e ID)
0005-1
0006-1
0010-1
0010-2
0011-1
Issue 02 (2017-02-25)
Alarm
Severit
Name
y
Mains
Minor
neutral
absent
Mains
Minor
undervoltag
e
Abnormal
Minor
bypass
voltage
Bypass
Minor
phase
reversed
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
1. Secure or connect the neutral
Cable
wire to the cabinet if it is loose
connections
or disconnected.
are incorrect.
2. Check that the neutral wire to
the power distribution system is
normal.
The mains
Check whether the mains voltage
is not
ranges from 80 V (excluding 80 V)
normal.
to 176 V. If no, the mains
monitoring circuit for the power
The
module is faulty. Replace the faulty
power
module.
module
sampling
circuit is
not
normal.
1. Check the bypass input voltage
The
or cable connections with a
bypass
multimeter.
voltage
range is
2. Check the voltage system and
not
bypass voltage thresholds
correctly
configured on the LCD.
set.
The
bypass
input
voltage is
not
normal.
1. Check the bypass input voltage
The
or cable connections with a
bypass
multimeter.
frequency
range is
2. Check the bypass input
not
frequency. Check the rated
correctly
frequency and frequency range
set.
configured on the LCD.
The
bypass
input
frequency
is not
normal.
The phase
Check whether the cable phase
sequence of
sequence is correct using a
the
multimeter. If no multimeter is
C Alarm List
277